Combustible gases
|
Hydrogen Sulfide
|
Carbon Monoxide
|
Oxygen
|
|
Gas detected and detection principle
|
Catalytic Combustion
|
Controlled potential electrolysis
|
Controlled potential electrosysis
|
Membrane galvanic cell
|
|
Detection range
|
0-100% LEL (1 digit / 1% LEL)
|
0-150 ppm (1digit/0.5ppm) service range 30.5-150ppm)
|
0-300 ppm (1 digit/1 ppm)
service range 101-300ppm
|
0-100% vol (1 digit / 0.1% vol)
service range 25.1-100%vol
|
|
Display
|
LCD (liquid crystal dot matrix 20 characters) displays outputs
of the 4 sensors simultaneously.
|
|
Alarm Functions
|
Alarm at more than 30 ± 5% LEL
|
Alarm at more than 10 ± 3 ppm
|
Alarm at more than 50 ± 15 ppm
|
Alarm at less than 18 ± 1.0% vol
|
|
Measurement accuracy
|
± 5% LEL (0-100%LEL)
|
± 1.5ppm (0-30 ppm)
|
± 10ppm (0-100 ppm)
|
± 0.7% vol (0-25%LEL)
|
|
Sampling method
|
Automatic sampling through built-in micro air pump
|
|
Response time
|
Within 40 seconds (to 90% of final reading, using 8m sampling tube)
|
|
Automatic calibration
|
Tunning ON automatically adjusts zero point for H2S,
CO and CH4 and adjusts span for O2
|
|
Warm-up time
|
Less than a minute (LCD display will display the message "WAIT
A MOMENT, PLS")
|
|
Power Supply
|
6 X size D dry cellls (SUM-1) or 100, 220VAC with power adaptor
|
|
Battery life
|
Approx. 18 hours continuous operation (by alkaline cells at normal
temperature / humidity)
|
|
Battery level and temperature display
|
Battery level is displayed on a bargraph alongwith ambient temperature
in celsius (1 digit/0.1° C). when the
battery is too low, the " REPLACE BATTERY" message will appear.
|
|
Operating temperature and humidity range
|
-10° C to + 40°
C, Max 90% RH
|
|
Gas Sampling tube
|
8m gas sampling tube with float
|
|
External alarm device
|
External alarm device with 8 m cable
|
|
Dimensions
|
105 (W) X 230 (L) X 175 (H) mm
|
|
Weight
|
Main Unit : Approximately 3.5 kg.
External Unit: Approximately 1.3 kg.
|
|
Standard Accessories
|
Sampling hose 8m long with floating probe, carrying case, AC adapter
(220V AC) with 5m cable, External alarm unit with 8m cable, dust
filter A (FE-2; 2 pcs.), dust filter B (FE-14; 2pcs.), Alcohol filter
(FE-19; 2pcs.), UM-1 (size D) dry cell battery (6pcs.)
|
|
Optional Accessories
|
Aluminium case, 1 meter sampling tube.
|